AC5000F series 40kW-180kW chilled water room level precision air conditioners

AC5000F series 40kW-180kW chilled water room level precision air conditioners adopt modular and integral structural solutions, compact structure, easy handling, full front maintenance, and effectively save the room area; The full series cooling capacity ranges from 40kW to 180kW, to provide more flexible configuration requirements.

consult

馬政發(fā)13911282237

  • Safe and reliable

    Use water as a refrigerant, close to nature, green, healthy, environmental protection; The use of high-performance EC centrifugal fan, high efficiency, small volume, low noise, high reliability, long life; With high reliability, the unit average time without failure MTBF≥ One hundred thousand hours.

  • Energy efficient

    Unit energy efficiency ratio (COP) up to 20 or more, to ensure that the equipment room and other places to achieve low PUE operation; The power distribution of the equipment is small, which can save the overall electrical investment, reduce the energy consumption of the unit, and low system operating costs and maintenance costs.

  • Intelligent control

    Adopt intelligent controller for PID adjustment, temperature control accuracy can reach ± 0.5℃, humidity control accuracy can reach ± 5%, to create a more stable operating environment for the equipment room; And standard RS485 communication interface; The electric valve with large flow coefficient is used to accurately adjust the water flow, reduce the water resistance, save energy consumption, and ensure stable water supply.

Application scenario

  • Data Center
    Such as supercomputing center, data center, cloud computing center

  • Medium and large switching room

  • Mobile room, computer room and electronic information Department
Supercomputing center, data center, cloud computing center. Medium and large switching room, mobile room, computer room and electronic information system room.
    Technical specification
    Model AC5000F-40 Series AC5000F-70 Series AC5000F-100 Series AC5000F-130 Series AC5000F-160 Series AC5000F-180 Series
    Function Optional constant temperature and humidity function
    Main Power supply 380V/3Ph/50Hz
    Inlet water Temperature (℃) 15℃
    Outlet Temperature (℃) 21℃
    Return-air condition 35℃/30%
    Total cooling capacity (kW) 42.6 72.0 100.3 132.9 165.5 189.2
    Cooling capacity (kw) 42.6 72.0 100.3 132.9 165.5 189.2
    Water flow (m³ /h) 6.1 10.3 14.7 19.8 23.7 27.1
    Water side resistance (kPa) 40.0 59.2 55.0 58.0 75.0 78.0
    Single cooling full load power (kW) 3.5 3.5 7.0 7.0 10.5 10.5
    Single cooling full load current (A) 5.3 5.3 10 11.8 16.0 16.4
    Circulating Air Volume (CMH) 9000 14800 24000 28400 38000 38500
    Number of fans 1 1 2 2 3 3
    Size: L * D * H (mm) 925*1000*1980 1820*1000*1980 2530*1000*1980

    Note: The above parameters are based on the ambient condition of 35℃/ 30%RH for return air. This technical parameter is only for selection reference, the actual parameter is subject to the software selection result.